Fire-resistant power cable NH - v. v. product characteristics and USES: this product has high fireproof performance, through direct combustion flame, in a certain period of time is not short circuit and short circuit fault, therefore, when the fire broke out, is beneficial to reduce the loss, low smoke zero halogen type cable to cable, especially suitable for fire requires high power, large buildings, railways, shipping, etc.
Product execution standard
Q/HHTZH009.2
Fire resistance in line with gb12666.6-90 requirements (IEC331)
1. Ac rated voltage: U0/U 0.6/1kV
2. High long-term operating temperature: flame retardant PVC J edge and sheath 70℃ and 105℃
Fluoroplastic J-edge and sheath 200℃ and 260℃
Crosslinked polyethylene j-edge 90℃
Low smoke halogen-free flame retardant polyolefin 70℃
Low smoke halogen-free flame retardant crosslinked polyolefin 90℃ and 120℃
3. Low ambient temperature: flame retardant PVC sheath: -40℃ for fixed laying, -15℃ for non-fixed laying
Fluorine plastic J-edge and sheath: fixed laying -60℃; Non-fixed laying -20℃
4. Fire resistance:
Comply with IEC331 | Flame temperature 750℃, combustion time 3h, cooling time 12h, additional rated voltage, additional 3A current |
Accord with GB12666.6 - class A | Flame temperature 950-1000℃, burning time 90min, additional rated voltage 3A current |
Accord with GB12666.6 - class B | Flame temperature 750-800℃, combustion time 90min, additional rated voltage 3A current |
5. Cable installation and laying temperature shall not be lower than 0℃
6. Recommended bending radius for laying: not less than 6 times of cable diameter for non-armored cable
Armored cable not less than 12 times of cable diameter
Fluorine plastic j-edge and sheath material cable should not be less than 8 times of cable diameter
Fire-resistant power cable
model | Product M said |
NH-VV | Flame retardant POLYvinyl chloride J-edge and sheath fire control cable |
NH-FF | Fluorine plastic J-edge and sheath fire resistant control cable |
NH-VDVD | Low smoke and low halogen flame retardant PVC FLAME retardant control cable with J-edge and sheath |
NH-YDYD | Low smoke halogen-free flame retardant polyolefin J-edge and sheath fire retardant control cable |
Note: Add 22 after armored cable model |